Macsolar Solar Inverter Fault & Error Messages

$
0
0

Macsolar Solar InverterThe proper installation of a Macsolar Solar Inverter would prolong its life. However, should there be any internal issues with the inverter this will be detected by the device and cause the Fault light to be displayed permanently. If the red light is on or if there is a green light without the yellow Run light a manual shutdown procedure is recommended.

There are also other faults that may require additional procedures. To make these more accessible, we have put together a list of faults, messages and possible actions from Macsolar Inverter user’s manual. If you are not very keen in performing below procedures, we recommend that you contact a qualified electrician to assist you.

Error No.

Information Message

Corresponding Action

0 Grid Vtg. Fault The grid voltage has exceeded the
permitted range according to local
grid regulations.
Following  causes  might  lead  to
this error:
• Grid voltage is too high or too  low  at  the  point  of common  coupling to the inverter.
• Grid impedance at the terminal of the inverter is too high.
For safety consideration, the
inverter will disconnect itself from
the grid for a short period of time,
and  it  will  reconnect  to  the  grid
automatically after a short period
of time if the grid voltage is back
to the permitted range.
• Check the grid voltage.
• Check the grid connection
of the inverter.
If  the  grid  voltage  exceeds  the permitted  range  because  of  local grid  conditions,  please  ask  the utility operator if the voltage can be adjusted at the feed-in point or if  changes  in  the  values  of  the monitored  operational limits are possible.
If the grid voltage that checked is within the permitted range, yet this error is still showing in the LCD screen, please contact Macsolar Serviceline.
  Grid Vtg.10min Fault The average grid voltage over 10 minutes   has   been   outside   the permitted range according to local grid regulations.
Following causes might  lead  to this error:
• Grid voltage is too high at the point   of   common coupling to the inverter.
• Grid impedance at the terminal of the inverter is too high.
For safety consideration, the inverter will disconnect itself from the grid for a short period of time, and it will reconnect to the grid automatically after a short period
of time if the grid voltage is back
to the permitted range.
•   Check the grid voltage.
• Check the grid connection
of the inverter.
If  the  grid  voltage  exceeds  the permitted  range  because  of  local grid  conditions,  please  ask  the utility operator if the voltage can be adjusted at the feed-in point or if  changes  in  the  values  of  the monitored  operational possible.
If the grid voltage that checked is within the permitted range, yet this error is still showing in the LCD screen, please contact
Serviceline.
2 Fac Fault The grid frequency has left the
permitted range.
For safety consideration, the
inverter will disconnect itself from
the grid for a short period of time,
and  it  will  reconnect  to  the  grid
automatically after a short period
of  time  if  the  grid  frequency  is
back to the permitted range.
• Within safety scope, check
the grid frequency and observe how often major deviations occur.
If  there  are  repeated  frequency turbulences  which  lead  to  this error,   please   ask   the   utility operator  if  modification  of  the operating parameter is possible.
If this error is not solvable, please contact Macsolar Serviceline.
3 Utility Loss The inverter has detected an error
in the cabling and cannot connect
to the grid.
Following causes might  lead  to
this error:
• Grid connection installation
failure.
• Cabling failure.
• Incorrect country setting.
• Check AC installation.
• Check grid connection.
•   Check if the country setting
is correct:
– Via LCD screen (please
refer to chapter 7.2
“Configuration”).
– Via the remote
communication:  setting
Parameter “Country”.
If this error is not solvable, please
contact Macsolar Serviceline.
4 High DC Bus The voltage of the Bus which
paralleling connected   with the
string is too high.
Following causes  might  lead  to
this error:
•   The DC   input   voltage
connected to the inverter is
too high.
• Sudden DC surge.
For safety consideration, the
inverter will shutdown itself.
• Please
disconnect the inverter
from the PV strings (see
chapter   6.5   “DC   side
Disconnection”)  or  else
the inverter might be
damaged.
• Check the  DC  voltage  of
the strings for adherence to
the maximum input voltage
of the inverter, before you
reconnect the inverter to
the PV strings.
5 GFCI Fault The inverter has detected a ground
fault in the PV generator.
• The installer of the PV
generator must solve the
ground  faults before you
re-connect the strings.
If this error is not solvable, please
contact Macsolar Serviceline.
6 Over-temperature  The   delivered   power   of   the
inverter was reduced below rated
power because   of abnormal
temperature within 0.5s.
Following causes  might  lead  to
this error:
•   At least one or more of the
thermally monitored
varistors are defective.
• Overheating inside.
• Not sufficient ventilation.
If this event occurs often:
• Please   ensure   sufficient
ventilation.
• Check the varistors.
If this error is not solvable, please
contact Macsolar Serviceline.
7 Varistor Fault At least one of the varistors from
the DC or AC  side  is  defected.
Following causes might  lead  to
this error:
• Varistor is bust due to contact Macsolar Serviceline. over-voltage protection.
If this event occurs:
Please  check  the  varistors
as   chapter   5.6   “Check
Varistors”.
If this error is not solvable, please
8 PV-Overvoltage The   DC   input   voltage   which
connects to the inverter is too high.
Following causes  might  lead  to
this error:
• The open-circuit voltage of
the PV generator is higher
than the maximum DC
input voltage    of the
inverter.
• Sudden DC surge.
• Junction temperature of
solar panel too low.
• Please immediately
disconnect the inverter
from the PV strings (see
chapter   6.5   “DC   side
Disconnection”)  or  else
the   inverter   might   be
damaged.
Check  the  DC  voltage  of
the strings for adherence to the
maximum input voltage of the
inverter, before you reconnect
the inverter to the PV strings.
9 Consistence Fault Following  causes  might  lead  to
this error:
• Interference device
If this event occurs often:
Please contact Macsolar
Serviceline.
10 Isolation Fault There  is  a  sudden  isolation  fault
which is detected by the inverter.
Normally this fault will only exist
for a very short period of time and
shall not have any bad influence to
the inverter.
If this event occurs often:
Please contact Macsolar
Serviceline.
11 DC INJ Fault The direct component of the AC
current  is  out  of  the  permitted
range.
If this event occurs often:
Please contact Macsolar
Serviceline.
12 Device Fault A  fault  has  occurred  in  one  or
more  major  components  of  the
inverter.
For safety consideration, the
inverter will shutdown itself.
If this event occurs:
Please contact Macsolar
Serviceline.
13 GFCI Device Fault The  internal  sensor  has  detected
that  the  GFCI  Device  is  out  of
function.
For safety consideration, the
inverter will shutdown itself.
If this event occurs:
Please contact Macsolar
Serviceline.
14 Comm. disturbed A fault has occurred in the internal
communication  of  the inverter.
However,  the inverter continues
feeding into the grid.
If this event occurs often:
Please contact Macsolar
Serviceline.
15 Current Sensor Fault A  fault  has  occurred  in  one  or
more current sensor of the inverter.
For safety consideration, the
inverter will shutdown itself.
If this event occurs:
Please contact Macsolar
Serviceline.
16 CPU Ref 2.5V Fault The CPU voltage that detected by
internal sensor is deviating the pre-
set 2.5V reference line.
If this event occurs:
Please contact Macsolar
Serviceline.
17 EEPROM R/W Fail Internal device fault.
For safety consideration, the
inverter will shutdown itself.
If this event occurs:
Please contact Macsolar
Serviceline.
18  DC INJ Device Fault A fault has occurred in the sensor
which detects the direct component
of the AC current.
For safety consideration, the
inverter will shutdown itself.
If this event occurs:
Please contact Macsolar
Serviceline.
19 Relay Fault A fault has occurred in the relay
which will automatically
disconnect  the  inverter  from  the
grid.
For safety   consideration,   the
inverter will shutdown itself.
If this event occurs:
Please   contact Macsolar
Serviceline.
20 AC-Overcurrent The   detected   AC   current   has
exceeded  the  pre-set  Max.  AC
Current.
Following  causes  might  lead  to
this error:
•   Short circuit happens in the
output circuit.
If this event occurs often:
Please contact Macsolar
Serviceline.

The full details are available in the Macsolar Inverter manual’s troubleshooting section. In case performing the steps above does not fix the issue and your Macsolar Solar Inverter is still within the warranty period you can contact the equipment installer or supplier.

If your Macsolar Solar Inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area contact Gold Coast Power Solutions here and we will be in touch to provide you with further assistance.

Need a quality solar inverter? We deliver Australia wide
Got A Question About Solar Power? Click Here For Answers!

The post Macsolar Solar Inverter Fault & Error Messages appeared first on Gold Coast Solar Power Solutions.