SolaX Solar Inverter Fault & Error Messages

$
0
0

SolaX Solar InverterSolaX Solar Inverter is a hybrid inverter that allows you to use your solar power at night after you charge your battery. It also directs power to any appliances operating throughout the day while storing unused power in the battery. You can also monitor its real-time performance through your iPhone or Android phone with the SolarMAN app.

But in case you see any issue, we have put together a list of faults and solutions from the users manual so you can work on your SolaX Solar Inverter. The list contains procedures for solving possible problems with the X-hybrid series inverters, and provides you with troubleshooting tips.

Should you decide to follow the recommended actions, please note that safety measures should be observed to avoid any risk of injury. Otherwise, contact a qualified electrician for assistance.

Faults Diagnosis and Solution
SPI Fault SPI communication fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
SCI Fault SCI communication fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
CAN1 Fault CAN communication fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
PV Config Fault PV Connection Setting Fault
• Resetting the PV connection
• Or seek help from us, if it cannot go back to its normal state.
Inv EEPROM Fault Inverter EEPROM fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Relay Fault Relay Fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Sample Fault The detection circuit Fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
RCD Fault Residual Current Device Fault
• Check the impedance of DC input and AC output.
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Fan1 Fault Fan Device Fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Check if the fan is stopped by dust or other foreign.
• Or seek help from us, if it cannot go back to its normal state.
Fan2 Fault
AC HCT Fault AC Current Sensor Fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
OverLoad Fault Over Load in EPS Mode.
• Turn off high power device , press “ESC” to restart the inverter.
• Or seek help from us, if it cannot go back to its normal state.
EPS OCP Fault Over Current in EPS Mode.
• Make sure the load power is within the EPS power range.
• Check if any nonlinear load is connect on the EPS. Remove this load
to check if can recover.
• Or seek help from us, if it cannot go back to its normal state.
DCI Device Fault DCI Device Fault
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
EPS Relay Fault EPS Relay Fault
• Disconnect PV+ , PV- , grid and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
TZ Protect Fault Over current Fault.
• Wait for a while to check if go back to normal status.
• Disconnect PV+ , PV- and battery, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Grid Lost Fault Grid is Lost.
• System will reconnect if the utility is back to normal.
• Or seek help from us.
Grid Volt Fault Grid Voltage Out of Range
• System will reconnect if the utility is back to normal.
• Or seek help from us.
Grid Freq Fault Grid Voltage out of range
• System will reconnect if the utility is back to normal.
• Or seek help from us.
PLL Lost Fault The Grid is Not Good.
• System will reconnect if the utility is back to normal.
• Or seek help from us.
Bus Volt Fault Bus Voltage out of Normal Range.
• Disconnect PV+ , PV- and battery, reconnect them.
• Check if the PV input is within the range of the inverter.
• Or seek help from us, if it cannot go back to its normal state.
AC5M Volt Fault The grid’s voltage is out of range for the last 5 Minutes.
• The system will back to normal if the grid is back
• Or seek for help from us.
Inv OCP Fault Inverter over current protection fault
• Wait for a while to check if back to normal.
• Or seek for help from us.
PV Volt Fault PV Voltage Fault
• Check the output of the PV voltage.
• Or seek for help from us.
AC10M Volt Fault The grid’s Voltage is out of range for the last 10 minutes.
• The system will back to normal if the grid is back
• Or seek for help from us.
Isolation Fault Isolation Fault
• Check the connection of the inverter.
• Or seek for help from us.
Temp Over Fault Temperature over the limitation
• Check if the fan is running normally.
• Check if the environment temperature is over limitation.
• Or seek help from us.
Fan1 Speed Fault Fan speed out of the normal range.
• Check if the fan is stopped by dust or other foreign.
• Or seek help from us, if it cannot go back to its normal state.
Fan2 Speed Fault
C1 Can Fault The battery group’s can communication fault.
• Reconnect the charger communication cable.
• Or seek help from us.
C1 Temp High The battery charger is over temperature.
• Check if the air ducting of the charger is blocked.
• Improve the working environment or reduce the charging or
discharging current.
• Or ,Seek help from us.
C1 FAN Fault The fan of the charger is broken.
• Check if the fan is working normally.
• Check if anything blocking the fan
• Or, Seek help from us.
C1 TZ Fault The protection of the charger fault.
• Wait for a while to check if back to normal.
• Or, Seek help from us.
C1 EEPROM Fault The charger’s EEPROM fault.
• Wait for a while to check if back to normal.
• Or, Seek for help from us.
C1 HCT1 Fault The charger’s current detection fault.
• Reconnect the charger.
• Or, Seek for help from us.
C1 HCT2 Fault
C1 Bus OVP The Bus voltage of the charger over limit.
• Wait for a while to check if back to normal.
• Or, Seek for help from us.
C1 Temp Low The charger is under temperature
• Improve the working environment of the charger.
• Or, Seek for help from us.
C1 Boost OVP The Boost voltage of the charger over limit.
•Wait for a while to check if back to normal.
•Or seek for help from us.
C1 Bat OVP The battery voltage is over limit.
•Wait for a while to check if back to normal.
•Or seek help from us.
C1 Charger OCP The charger is over current protected.
•Wait for a while to check if back to normal.
•Or seek help from us.
C1 Boost OCP The boost current of the charger is over limit.
•Wait for a while to check if back to normal.
•Or seek help from us.
CT Fault The CT or the meter is not connected well.
•Check the connection of the CT or the meter.
•Or seek help from us.
RC Fault DCI over current protection Fault.
•Wait for a while to check if back to normal.
•Or seek help from us.
DCI OCP Fault DCI over current protection Fault.
•Wait for a while to check if back to normal.
•Or seek help from us.
Other device Fault Other device fault.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
SW OCP Fault Over current fault detected by software.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
DM9000 Fault Network DSP fault.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
RTC Fault RTC Fault
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Mgr EEPROM Fault Manager EEPROM Fault.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Mgr CAN Fault Manager CAN Fault

• Turn off the PV, battery and grid , reconnect them.

• Or seek help from us, if it cannot go back to its normal state.

C1 SPI Fault Charge can communication fault.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
Fault Charge over current detected by hardware C1 TZ
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.
C1 FAN Fault Charge FAN Fault.
•Check if the fan is blocked.
• Or seek help from us, if it cannot go back to its normal state.
C1 sample Fault Charge sample fault.
•Turn off the PV, battery and grid, reconnect them.
• Or seek help from us, if it cannot go back to its normal state.

If you need the full information on this, you can find them on the SolaX solar inverter manual’s Troubleshooting section.  Should you follow the troubleshooting steps above but the issue is not fixed on your SolaX solar inverter check if it’s still within the warranty period so you can contact the equipment installer or supplier.

If your SolaX Solar Inverter is outside the warranty period we suggest that you contact a professional solar power expert. If you’re in the Gold Coast or Brisbane area contact Gold Coast Power Solutions here and we will be in touch to provide you with further assistance.