Clenergy SPH Solar Inverter Error Messages

$
0
0

Clenergy solar power inverter manual and datasheetTo make it easier to determine actions to take on common Clenergy SPH Solar Inverter Error Messages, Gold Coast Solar Power Solutions have put together a list of fault displays, explanations and resolutions. If you encounter any of these errors on your Clenergy SPH inverter please note that those shown in bold letters are to be carried out by a qualified electrician.

View the Clenergy SPH solar inverter user manual here.

Fault

Display

Possible Actions

System No Utility 1.No grid voltage. Check the grid voltage by multi-meter.
2.Check grid connection, such as wire and connector to the inverter.
3.Check breaker between inverter and grid; if it is tripped, DO NOT CLOSE again, get an electrician to check the wiring and inverter.
Grid Fault 1.Wait for grid power to return to normal. If the grid returns to normal, the inverter will start again automatically within 5 minutes.
2.Check the grid voltage and frequency by multi-meter. Make sure grid voltage and frequency meet the specifications.
3.Contact your inverter service representative to discuss adjusting the operating range, if permitted by the electricity provider.
Impedance Fault 1.The grid impedance is higher than the permissible value.
2.Wait for grid power to return to normal. If the grid returns to normal, inverter will start again automatically within 5 minutes.
3. Check the wires between inverter and grid. For high impedance connections, get an electrician to increase the wire size.
4. Contact your inverter service representative to discuss adjusting the operating range, if permitted by the electricity provider.
Isolation Fault 1.Check the impedance between PV (+) & PV (-) and earth ground. The impedance must be larger than 8M . If the impedance is low a ground fault may exist in the PV array or wiring. Contact your PV array service provider or electrician.
2.If above actions do not fix the problem, the isolation detection circuit may be faulty. Contact your inverter service representative.
Ground I Fault 1.This is caused by too high ground current.
2.Disconnect the inverter from the grid power. Check the AC wiring and connection system.
3.After the cause is cleared, reconnect the grid power. Check the status of the inverter.
4.If above actions do not fix the problem, the GFCI circuit may be faulty. Contact your inverter service representative.
Inverter Failure Over Temperature 1.The internal temperature is higher than specified normal value.
2.Reduce the ambient temperature by shading or ventilation improvements or move inverter to cooler place.
3.If this is not effective, a temperature sensor may be faulty. Contact your inverter service representative.
PV Over Voltage 1. Check the PV open-circuit voltage. This should be less than 500VDC.
2.  If the PV voltage is much less than 500VDC (e.g. <430V), measure the DCV by multi-meter, compare the readings on meter and LCD.
If the readings differ by >5%, contact your inverter service representative.
Device Fault 1.This is caused by an inverter malfunction.
2.Disconnect PV (+) or PV (-) from the input, start the unit again.
3.If it does not work, contact your inverter service representative.
Consistent or Mismatch Fault 1.This is caused by inconsistent values between the main (master) and redundant (slave) controllers of the inverter.
2.Disconnect PV (+) or PV (-) from the input, start the unit again.
3.If this does not work, contact your inverter service representative.

Here are some more Clenergy SPH Solar Inverter Error Messages and explanations that you may see on its screen.

Error Message  Explanation
No Utility  Grid voltage is not detected
PV Over Voltage  PV voltage is too high
DC Bus High  Internal DC bus voltage is too high
DC Bus Low  Internal DC bus voltage is too low
Over Temperature  Internal temperature is too high
Grid Fault  Grid voltage or frequency is out of range
Device Fault  Internal fault with inverter circuits
Isolation Fault  PV panel ground isolation problem
Impedance Fault  Grid impedance fault (or grid disconnected)
Ground I Fault  Grid output ground leakage current too high
Relay Failure  Grid output relay failure
DC INJ High  Grid DC injection too high
Ref 2.5V Fault  2.5V reference voltage internal circuit fault
DC Sensor Fault  Grid DC current sensor internal fault
GFCI Fault  Ground Fault Current Interrupt fault
Sci Fault  Internal Master/Slave communication fault
Consistent Fault  Internal Master/Slave value mismatch fault
CPU Ver Mismatch  Internal Master/Slave firmware incompatible
EEPROM Fault  Internal non-volatile memory fault
Grid V Mismatch  Internal Master/Slave grid voltage mismatch
Grid F Mismatch  Internal Master/Slave grid frequency mismatch
Grid Z Mismatch  Internal Master/Slave grid impedance mismatch
GFCI Mismatch  Internal Master/Slave ground fault value mismatch
DC Curr Mismatch  Internal Master/Slave grid DC current mismatch

Clenergy SPH Solar Inverter Error MessagesIf you want to find out more of these Clenergy SPH Solar Inverter Error Messages, the full details are in the Clenergy manual’s Troubleshooting section. In case the resolution procedure does not fix the issue, contact your equipment installer or supplier for assistance if Clenergy SPH inverter is still within the 5-year warranty period. If your inverter is outside the warranty period we recommend that you get the assistance of professional solar power experts. If you’re in the Gold Coast or Brisbane area contact Gold Coast Power Solutions here and we will be in touch to provide you with further assistance.

View the Clenergy SPH solar inverter user manual here.